Journal article
Power Flow in Four-Wire Distribution Networks - General Approach
RM Ciric, A Padilha Feltrin, LF Ochoa
IEEE Transactions on Power Systems | IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC | Published : 2003
Abstract
The neutral wire in most power flow software is usually merged into phase wires using Kron's reduction. Since the neutral wire and the ground are not explicitly represented, neutral wire and ground currents and voltages remain unknown. In some applications, like power quality and safety analyses, loss analysis, etc., knowing the neutral wire and ground currents and voltages could be of special interest. In this paper, a general power flow algorithm for three-phase four-wire radial distribution networks, considering neutral grounding, based on backward-forward technique, is proposed. In this novel use of the technique, both the neutral wire and ground are explicitly represented. A problem of ..
View full abstractGrants
Awarded by Fundação de Amparo à Pesquisa do Estado de São Paulo