Journal article
CFD analysis of ejector in a combined ejector cooling system
E Rusly, L Aye, WWS Charters, A Ooi
International Journal of Refrigeration | ELSEVIER SCI LTD | Published : 2005
Abstract
One-dimensional ejector analyses often use coefficients derived from experimental data for a set of operating conditions with limited functionality. In this study, several ejector designs were modelled using finite volume CFD techniques to resolve the flow dynamics in the ejectors. The CFD results were validated with available experimental data. Flow field analyses and predictions of ejector performance outside the experimental range were also carried out. During validation, data from CFD predicted the entrainment ratios with greater accuracy on definite area ratios, although no shock was recorded in the ejector. Predictions outside the experimental range - at operating conditions in a combi..
View full abstract