Journal article
Testing of normal-and high-strength concrete walls subjected to both standard and hydrocarbon fires
T Ngo, S Fragomeni, P Mendis, B Ta
ACI Structural Journal | AMER CONCRETE INST | Published : 2013
Abstract
Ten large-scale concrete wall panels were tested in this study. Four walls were of normal-strength concrete (NSC)-two of which were axially loaded at an eccentricity of 10 mm (0.39 in.) and two with no load-and exposed to either standard or hydrocarbon fires. Four identically dimensioned high-strength concrete (HSC) walls were also tested using these variables. An additional two HSC walls, with polypropylene fibers added, were tested under hydrocarbon fire conditions only. All walls were tested in a vertical position in a large furnace and supported at the top and bottom only. The results indicate that all concrete wall panels exposed to the standard fire tests survived the 120-minute fire p..
View full abstractGrants
Funding Acknowledgements
This project was partlially funded by the Vietnamese government and the Vietnam Institute for Building Science and Technology (IBST). The authors would also like to thank the staff at IBST, where the experimental work was conducted.